Miscellaneous (Environmental) Discrete Telemetry Cable Installation - Alcatel-Lucent 1665 Installation Manual

Data multiplexer
Hide thumbs Also See for 1665:
Table of Contents

Advertisement

Cable and fiber installation
............................................................................................................................................................................................................................................................
Table 3-23 Office alarm connections
Miscellaneous (environmental) discrete telemetry cable
installation
Description
The miscellaneous (environmental) discrete telemetry access allows the maintenance
center to control and monitor equipment collocated with the Alcatel-Lucent 1665 DMX
high-capacity shelf.
The environmental control feature enables the maintenance center to remotely initiate up
to four contact closures at the remote terminal (RT) for equipment operation such as
pumps, generators, etc.
The environmental alarm status indications allow up to 23 miscellaneous user-settable
alarm status indications (SI) at the remote terminal for transmission toward the central
office.
............................................................................................................................................................................................................................................................
Alcatel-Lucent 1665 DMX R9.0
365-372-304R9.0 Issue 2
July 2010
Conn.
Pin#
Color
J12-J13
1
BL-W
2
W-BL
3
O-W
4
W-O
5
G-W
6
W-G
7
BR-W
8
W-BR
9
S-W
10
W-S
11
BL-R
12
R-BL
Notes:
1. The SYSCTL circuit pack reports office alarms.
2. The connection to the central office alarms from P12 is run for each
DMX
assembly when used in a miscellaneously-mounted individual
application or from the first 1665 DMX assembly when mounted in a typical
bay arrangement.
Miscellaneous (environmental) discrete telemetry cable
Designation
Name
RYMJV1
Major Alarm Visible
RYMJV2
Major Alarm Visible Return
RYMJA1
Major Alarm Audible
RYMJA2
Major Alarm Audible Return
RYMNV1
Minor Alarm Visible
RYMNV2
Minor Alarm Visible Return
RYMNA1
Minor Alarm Audible
RYMNA2
Minor Alarm Audible Return
RYCRV1
Critical Alarm Visible
RYCRV2
Critical Alarm Visible Return
RYCRA1
Critical Alarm Audible
RYCRA2
Critical Alarm Audible Return