CAST ZFP Analogue Addressable Fire Alarm Panel
Appendix 6 – CAST ZFP Technical Specification
Power Supply and Charger
Mains supply operating voltage
Rated current
Battery charge capacity (C)
Max. VRLA battery size
Power rating
Max. internal battery resistance (Ri max.)
Maximum power output voltage 'V max'
Minimum power output voltage 'V min':
Output ripple voltage (peak-to-peak)
Mains supply/battery charger monitored for failure
Batteries monitored for disconnection and failure
Earth fault monitoring
Loop Driver Specification (programmable & monitored)
Number of loops
Connector block type
Loop driver PCB type
Max. output current per loop
Communication Protocols
Maximum number of addressable devices
Type of cable / Max. cable length per loop
Max. allowable loop impedance (each conductor)
Max. cable capacitance
Auto-polling from each loop end
Line monitored for o/c and s/c faults
Conventional Sounder Circuits (programmable & monitored)
Number of circuits
Connector block type
EOL resistor (supplied)
Output voltage
Type of cable / Max. cable length per circuit
Line monitored for o/c and s/c faults
Auxiliary Inputs (programmable & monitored)
Number of auxiliary inputs
EOL resistors (supplied)
Trigger resistors (supplied)
Line monitored for o/c and s/c faults
Relay Outputs (programmable)
Number of relay outputs
Relay type
Relay output
Fault relay
24Vdc auxiliary power output
Fuses (compliant to IEC EN60127 Pt2)
Primary fuse (F1)
Battery fuse (F2)
Communication Buses
Pager (ESPA protocol) / DECT telephone system /
Graphics Interface
Graphics Interface / Diagnostics
Peripheral Bus (A-Bus)
PC interface
A-Bus PCBs
A-Bus peripheral PCBs
Indicators and Controls
Standard provision
Display
Zonal indicators
Switches
Switch & Indicator module capacity
(one of these must be a Z41 Control/Display module)
CAST ZFP Modules
Control / Switch & Indicator Modules
Installation and Programming Manual  Approved Document No. DFU5030000 Rev 4  Page 58 of 60
600 mΩ if DIP Switch 2 OFF (Down) - Normal Operation [Approved for EN54-4 applications.]
480 mΩ if DIP Switch 2 ON (Up) - Maintenance Only. [Not approved for EN54-4 applications.]
≤ 320 mV over the full input and output range of the PSU
Plug-on type, largest acceptable cable size 2.5mm
Main 1-Loop PCB, Main 2-Loop PCB, 2-Loop PCB
450mA (Voltage: 40V max.)
255 devices per loop (maximum of 512 detectors / call points per panel).
Maximum of 40 loop sounders per loop, or 30 loop sounder VADs per loop.
Fire resistant screened cable, min. size 1mm
2 x 1A outputs. Protected by resettable overload circuit.
Plug-on type, largest acceptable cable size 2.5mm
6800 ohm, 5% tolerance, 0.25W
Fire resistant screened cable, min. size 1mm
2 (Connect to 0V to trigger, Max. input voltage 27Vdc non-latching)
6800 ohm, 5% tolerance, 0.25W
2 x programmable auxiliary relays; 1 x failsafe fault relay; 1 x 24Vdc (100mA) aux power output
Volt-free, single pole changeover
Active when faults are present or on total power failure
19.5V minimum, 28V maximum. Max. current 100mA.
T 2 A H 230 V, 20 mm ceramic (T = Time Delay; H = High Breaking Capacity)
7.5 A MINI
1 x RS485 connector. Allows the connection of A-Bus PCBs (15 maximum per panel)
Galvanically isolated USB connector (provided on the Z41 Control/Display module)
See Section 6 for a summary of features
All models include a Z41 Control/Display module which comprises a full colour 4.3 inch touchscreen,
all mandatory EN 54 indicators, 3 spare LEDs and a keyswitch allowing direct access to AL2.
LCD Touchscreen, 4.3 inch, 480 x 272 pixel, 24 bit, 16M RGB colour.
Up to 40 separate programmable LEDs available via Switch & Indicator expansion modules.
Multiple switches available via Switch & Indicator expansion modules.
Control/Display module c/w LCD, touchscreen, keyswitch, 16 LEDs.
40 zone indicator module c/w 5 switches, 10 LEDs.
STANDARD CABINET
230V
50/60Hz
1.3A r.m.s.
7Ah min. to 17Ah max.
2 x 12V, 17Ah
'I max a' = 0.84A
'I max b' = 3.1A
'I min' = 0.2A
30V
20 V ± 2% with mains On
21 V ± 2% with mains Off
 Yes
 Yes
 Yes
1 to 4
C-TEC's CAST
2
/ 1km max. length
< 10 ohm
.27µF
 Yes
 Yes
19.5V min.; 28V max.
2
/ 1km max. length
 Yes
470R, 0.25W
 Yes
1A, 30Vdc (max.)
®
automotive blade fuse
1 x RS232 connector
1 x RS485 connector
2
2
2
Part No. Z41.
Part No. Z48.