Change Access Level 2 (Al2) Code; Change Access Level 3 (Al3) Code; Panel Notes - C-TEC CAST ZFP Installation, Maintenance & Operating Manual

Analogue addressable fire alarm control panel
Hide thumbs Also See for CAST ZFP:
Table of Contents

Advertisement

CAST ZFP Analogue Addressable Fire Alarm Panel
The panel display will identify the precise location of the loop break between loop devices 'X + Y', for example:
8.5.10

Change Access Level 2 (AL2) Code

Enter AL3 (4444) > Engineering Functions press the
appears:
8.5.11

Change Access Level 3 (AL3) Code

This function is used to change the four-digit code needed to enter the panel's access level 3 menu options.
Enter AL3 (4444) > Engineering Functions press the
Follow the same procedure as detailed in section 8.5.10.
Note: If the code is lost or not known, the building owner will need to email C-TEC Technical Dept. (available
@ www.c-tec.com) to request a new code generating.
8.5.12

Panel Notes

Enter AL3 (4444) > Engineering Functions > Panel Notes.
This function allows panel specific comments to be written by an authorised systems engineer. These comments
are editable.
When selected, press anywhere in the Comments window (shown below left) and in the next window that
appears use the touchscreen's QWERTY keyboard to add pertinent notes about the panel (shown below right).
Installation and Programming Manual  Approved Document No. DFU5030000 Rev 4  Page 40 of 60
Note that short and open circuit are latching faults.
Fix the open or short circuit at the location identified by the
panel.
Enter AL3 (4444) or AL2 (3333) press
The panel returns to normal if the fault is fixed.
Use the touchscreen's numeric keypad buttons to enter
the new access level 2 code. After the fourth digit has
been entered, the panel will request you confirm the new
code by re-entering it.
Enter the code again by pressing the buttons in the same
sequence. If the two codes match, the panel will accept
the code and you will be taken back to the engineering
menus. If you type an incorrect confirmation code you
will be prompted to start the new code entry sequence
again.
button.
button.
button and the window below

Advertisement