CAST ZFP Analogue Addressable Fire Alarm Panel
6 A-BUS (Optional)
A-Bus enhances the functionality of the CAST ZFP system by connecting peripheral PCBs which provide
additional relay outputs, digital I/O, sounder circuits and detection zones.
The A-Bus RS485 network protocol allows the interconnection of up to 15 A-Bus PCBs per Main 1 or 2-Loop PCB
using 2 core screened cable (plus 2 core for power). A-Bus PCBs are normally installed within a CAST ZFP panel
but can also work up to a distance of 1km for non-EN 54-2 functions. Two A-Bus PCB sizes are available; full and
half size. If required, a full size PCB (Relay & Digital I/O only) can be scored in the middle to produce a half size
PCB. The A-Bus PCBs are programmed using CAST ZFP Programming Tools (Part No. ZTOOLS).
6.1

Z11/Z12 Relay PCB and Z13/Z14 Digital I/O PCB Features

Feature
A-Bus PCBs:
Cabling:
Protocol:
Installation:
Number of PCBs:
PCB sizes (mm):
Powered from:
Common features:
Relay PCB (Z11/Z12) features:
(8-way PCB shown below)
Page 21 of 60  Approved Document No. DFU5030000 Rev 4  Installation and Programming Manual
Details
CAST ZFP 4-way Relay PCB (half size). Part No. Z11.
CAST ZFP 8-way Relay PCB (full size). Part No. Z12. Non-EN54-2 approved.
CAST ZFP 8-way Digital I/O PCB (half size). Part No. Z13.
CAST ZFP 16-way Digital I/O PCB (full size). Part No. Z14. Non-EN54-2 approved.
2 core screened cable (plus 2 core for power).
RS485, 19200 BAUD, 8 Data, no Parity, 1 stop bit.
PCBs normally installed within a CAST ZFP panel but may be extended up to
1km for non-EN 54-2 functions.
Connect up to 15 A-Bus PCBs per Main 1 or 2-Loop PCB.
Half size: 80 w x 70 h x 30 d.
Full size: 80 w x 150 h x 30 d.
Main 1 or 2-Loop PCB (dependent on model) or an external EN 54-4/A2 PSU (not
supplied).
24V supply inputs.
A-Bus RS485 connections (B, A, 0) to Main 1 or 2-Loop PCB.
Comms connections (PL1/PL2); Power In/Power Out connections (PL5/PL6).
15 available addresses (set using DIP switch SW1, see section 6.2).
Isolated RS485 multi drop.
LED indication for polling and power.
Standard 5mm fixed PCB connectors, accept up to 2.5mm
Common features (as above).
1A 30V single pole contacts.
Full size PCB can be scored in the middle to produce a half size PCB.
Full size provides 8-way option; half size provides 4-way option.
Each relay output is programmable using CAST ZFP Programming Tools.
Separate LED indication provided for each relay.
2
cable.