Enable/Disable Zones; Enable/Disable Devices; Enable/Disable Input Groups - C-TEC CAST ZFP Installation, Maintenance & Operating Manual

Analogue addressable fire alarm control panel
Hide thumbs Also See for CAST ZFP:
Table of Contents

Advertisement

CAST ZFP Analogue Addressable Fire Alarm Panel
8.8.2
Enable/Disable Zones
This function allows you to disable (and re-enable) selected zones from reporting fires, faults, pre-alarms, etc.,
and is normally used to temporarily disable detectors including manual call points in a selected zone. For
example, in areas where work is being carried out that could trigger an erroneous fire alarm.
Enter AL3 (4444) > Disablement Functions press the
the one shown below left will appear.
Press the
and
buttons (or use the scroll bar) to scroll the display through all available zones. Toggle
a selected zone's enabled/disabled state by pressing the individual zone description display (Zone 1 status is
changed from 'Enabled' to 'Disabled' in the example above). After changing a zone's status, press the
button to escape. Note: The panel will retain the disablement settings until they are manually reset to their
normal settings. It is strongly recommended all disablements are cleared when no longer necessary.
8.8.3
Enable/Disable Devices
This function allows system devices to be disabled (and re-enabled) from reporting fires, faults, pre-alarms,
etc., and is normally used to temporarily disable detectors/manual call points that are nuisance tripping.
Enter AL3 (4444) > Disablement Functions press the
below will appear:
8.8.4

Enable/Disable Input Groups

This function is used to disable (and re-enable) one or more Input Groups from activating.
Input Groups include detectors (smoke, heat, multi), MCPs, inputs of I/O units, panel keyswitches, inputs of A-
Bus PCBs, monitored inputs.
Enter AL3 (4444) > Disablement Functions press the
operating procedure previously listed in section 8.8.2.
Installation and Programming Manual  Approved Document No. DFU5030000 Rev 4  Page 50 of 60
Press the By Zone button to select and disable all devices
within a specific zone, or press the By Address button to
select and disable individual devices by entering their loop
number and address.
Follow the same operating procedure previously listed in
section 8.8.2.
button and a window similar to
button and the window shown
button and follow the same

Advertisement