CAST ZFP Analogue Addressable Fire Alarm Panel
8.6.2

Auto Address

An alternative function to Auto Address is the LOOP LEARN menu option (see section 8.6.1 for details).
During an auto address the panel automatically assigns an address to each loop device in sequentially
wired order.
CAUTION: USING THIS OPTION WILL COMPLETELY ERASE THE PANEL'S DATABASE OF
STORED LOOP DEVICE INFORMATION. THEREFORE, USE WITH EXTREME CARE.
Only select this option if the panel has not previously been programmed, or if you want to program an existing
system as if it were a new, clean system and you are confident to proceed.
Enter AL3 (4444) > Commissioning Functions press the
below appears, for example.
A progress bar will be shown during the auto address process. DEPENDING ON THE SIZE OF THE
INSTALLATION, THE LOOP LEARN MAY TAKE SOME TIME. WAIT FOR THE PROCESS TO
COMPLETE! ONCE LEARNED, WAIT FOR AT LEAST 5 MINUTES TO ALLOW THE SYSTEM TO
SYNC WITH THE DEVICES.
If any fault messages are displayed at the panel, enter AL3 (4444) or AL2 (3333) and press
A
FTER A SUCCESSFUL AUTO ADDRESS YOU WILL HAVE A
S
1,
8.6.1
EE TABLE
SECTION
Find New Devices Option
The Find New Devices option may be used if a new device has been added to a loop and you do not want to
erase the stored loop device data.
Select the loop, select the Find New Devices tick box option and press the
The panel will start to learn the loop from the last known address in its memory. Existing data will not be
overwritten, e.g. device names, zone and group allocation, etc., will remain unchanged. The panel will only find
new devices which it will automatically allocate to the next available 'unpopulated' loop address.
Depending on the installation size the learn process can take several minutes. Wait for the process to
complete. Once learned, wait for at least 5 minutes to allow the system to sync with the devices.
When the auto address process is complete, enter AL3 (4444) > Commissioning Functions >
Device Manager to check the updated loop configuration.
Installation and Programming Manual  Approved Document No. DFU5030000 Rev 4  Page 44 of 60
FOR THE DEFAULT DEVICE ASSIGNMENT FOLLOWING AN AUTO ADDRESS
button and the window shown
Select the loop(s) you want the panel to auto address
(Loop 1 and Loop 2 are shown selected), then press the
button.
The panel will ask for confirmation.
Press the 'tick'
button to proceed.
"
"
,
ONE OUT
ALL OUT
FIRE ALARM SYSTEM
The panel will ask for confirmation.
Press the 'tick'
button to proceed.
button to clear.
.
.
button as shown below: