5.16 Connecting Mains to the Panel's PSU

THE PSU IS CLASS 1 EQUIPMENT AND MUST BE EARTHED.
The panel's EN 54-4 PSU is a mains to regulated DC power supply providing 5A @ 24Vdc nominal. Combining
the functions of a PSU, battery charging unit and battery monitoring unit, it is fully compliant with EN 54-4:1997
+ A1:2002 + A2:2006. For compliance with EN 54-4 the PSU must be closely coupled with the CIE.
Remove the protective cover of the PSU and terminate the mains cable at the power supply's PCB connector
block CONN1 (see Fig.10 below). After terminating, refit and secure the cover.
DO NOT CONNECT MAINS SUPPLY TO THE PSU UNTIL THE INSTALLATION IS COMPLETE
AND THE PANEL IS READY TO BE TESTED.
Fig.10 – 5A PSU Layout and Mains Connection Details
Fig.10 key:
Mains Cable
A
Must be fire resistant, segregated from extra low voltage cables and only
enter the panel through the top knockouts.
Mains Connector (CONN1)
B
L=Live, N=Neutral,
Earth Distribution Tag
C
DO NOT operate the PSU without first connecting this strap to the base
earth distribution post
D
Mains Fuse (F1) Exposed live parts under fuse cover. Isolate before
Cable Cover
Exposed live parts under cable cover. Isolate first, then remove the small
E
cover by loosening its single retaining screw which is retained in the cover.
Only operate the PSU with this cover securely fitted
F
Display & Data Connector (PL2)
Hazardous Voltage Present LED
When lit red, hazardous voltages are present on the components
and copper under the PSU's cover. Allow to discharge for at
G
least 5 minutes before removal & handling. DO NOT TOUCH
UNTIL EXTINGUISHED!
Page 19 of 60  Approved Document No. DFU5030000 Rev 4  Installation and Programming Manual
=Earth. Terminate mains cable to this connector.
H
Battery Fuse (F2)
I
Supply Output
J
Battery Connector (CONN7)
DIP Switches 1, 2, 3, 4 (SW1)
K
removal.
OFF (Down) = Defaults
Cat 5 Connector (PL1)
L
Connects to PL10 on Main 1 or 2-Loop PCB
Battery Charge Inhibit (CONN6)
M
Configurable Input/Output (CONN6)
N
Fault Relay
(CONN4)
(CONN3)