A-Bus Dip Switch Address Settings - C-TEC CAST ZFP Installation, Maintenance & Operating Manual

Analogue addressable fire alarm control panel
Hide thumbs Also See for CAST ZFP:
Table of Contents

Advertisement

CAST ZFP Analogue Addressable Fire Alarm Panel
Feature
Digital I/O PCB (Z13/Z14)
features:
(16-way PCB shown below)
Digital I/O Terminations
Note: Terminations to 'IO1' is shown as an example below,
other I/O terminals to be wired similarly.
6.2

A-Bus DIP Switch Address Settings

Each PCB's address is set using Bits 1 to 4 on the 4-way DIP switch (SW1).
DIP switch up (ON) = 1, DIP switch down (OFF) = 0. DO NOT use address 0.
Use a small screwdriver to set the switches and ensure the switches are fully
pushed home, up or down.
Refer to table below for address settings.
DIP position
Address
1 2 3 4
0
DO NOT USE
1
0 0 0 1
2
0 0 1 0
3
0 0 1 1
4
0 1 0 0
5
0 1 0 1
6
0 1 1 0
7
0 1 1 1
Note: The DIP switch address setting for each PCB (maximum of 15 addresses) should be the same address
allocated using the CAST ZFP Programming Tools (Part No. ZTOOLS).
Installation and Programming Manual  Approved Document No. DFU5030000 Rev 4  Page 22 of 60
Details
Common features (as above).
Open collector outputs (100mA sink).
Full size PCB can be scored in the middle to produce a half size PCB.
Full size provides 16-way option; half size provides 8-way option.
Each I/O is programmable using CAST ZFP Programming Tools.
1 LED for any input; 1 LED for any output.
DIP position
Address
1 2 3 4
8
1 0 0 0
9
1 0 0 1
10
1 0 1 0
11
1 0 1 1
12
1 1 0 0
13
1 1 0 1
14
1 1 1 0
15
1 1 1 1
Use Bits 1-4 on the DIP switch
to select the PCB's address
(address 1 set in above example).