Z16 Zone & Conventional Sounder Pcb Features - C-TEC CAST ZFP Installation, Maintenance & Operating Manual

Analogue addressable fire alarm control panel
Hide thumbs Also See for CAST ZFP:
Table of Contents

Advertisement

CAST ZFP Analogue Addressable Fire Alarm Panel
6.4
Z16 Zone & Conventional Sounder PCB Features
Feature
A-Bus PCB (Z16):
Cabling:
Protocol:
Powered from:
No. of Detection Zones:
No. of Sounder Circuits:
Installation:
Number of PCBs:
PCB size (mm):
Common features:
Zone Sounder PCB
(Z16) features:
(shown below)
Installation and Programming Manual  Approved Document No. DFU5030000 Rev 4  Page 24 of 60
Details
CAST ZFP Detection Zone & Conventional Sounder PCB (full size). Part No. Z16.
2 core screened cable (plus 2 core for power).
RS485, 19200 BAUD, 8 Data, no Parity, 1 stop bit.
Note: We recommend an Aux EN 54-4/A2 PSU (external to the CAST ZFP panel – not supplied).
The PCB terminal labelled 'Ex' is used to report a fault from the Aux PSU. It is triggered from
an active IO signal from an open collector (O/C), or volt-free (with 0V common) relay O/P.
4 x Conventional detection zones, each with a maximum of 10 conventional devices.
2 x 1A Conventional sounder outputs. Programmable and monitored.
PCBs normally installed within a CAST ZFP panel but may be extended up to 1km for
non-EN 54-2 functions.
Connect up to 15 A-Bus PCBs per Main 1 or 2-Loop PCB.
67 w x 165 h x 17 d.
24V supply inputs.
A-Bus RS485 connections (B, A, 0) to Main 1 or 2-Loop PCB.
Comms connections (PL2/PL3); Power In/Power Out connections (PL5/PL6).
15 available addresses (set using DIP switch SW1, see section 6.2).
Isolated RS485 multi drop.
LED indication for polling and power.
Standard 5mm fixed PCB connectors, accept up to 2.5mm
Common features (as above).
4 x Conventional zone inputs.
2 x 1A Monitored, conventional sounder outputs.
Each circuit is programmable using CAST ZFP Programming Tools.
Note: The Z16 DOES NOT have the facility to 'pulse sounders'.
Separate LED indication provided for each zone and sounder circuit.
2
cable.

Advertisement

Table of Contents
loading

Table of Contents