CAST ZFP Analogue Addressable Fire Alarm Panel
8.8.5

Enable/Disable Output Groups

This function is used to disable (and re-enable) one or more Output Groups from activating.
Output Groups include loop sounders and conventional sounders, VADs, outputs of I/O units, outputs of A-Bus
PCBs, panel relays.
This function is typically used to disable, for example, auto-diallers and other ancillary equipment from
activating during routine maintenance.
Enter AL3 (4444) > Disablement Functions press the
operating procedure previously listed in section 8.8.2.
8.8.6

Enable/Disable Panel Printer

This function only applies to panels with an integrated printer fitted.
8.8.7

Clear All Disablements

This function is used to globally clear all current disablements on the system.
Enter AL3 (4444) > Disablement Functions press the

Set the Panel's Time and Date

8.9
This function is used to set the panel's time and date, which is required for accurate logging of events in the
panel's log. The panel has a real-time 24 hour clock with default time and date settings. An automatic DST
(Daylight Saving Time) option is available which will automatically adjust the panel's clock one hour forward
on the last Sunday in March and one hour backward on the last Sunday in October.
Enter AL3 (4444) press the
Adjust the time and date using the touchscreen's numeric keypad and
daylight saving time by pressing the DST tick box.
When correct, press the

8.10 Show Supervisory Events

This function is only available if relevant to the panel's status, i.e. if access level 3 supervisory events have been
programmed by an authorised systems engineer.
Enter AL3 (4444) press the
related events, e.g. class change, gas shut off valve operated, panel keyswitch activated, emergency lighting
system signals, etc.
Page 51 of 60  Approved Document No. DFU5030000 Rev 4  Installation and Programming Manual
button and a window similar to the one shown below appears.
button to return to the main access level 3 menus.
button. The display shows all access level 3 non-fire, non-fault
button and follow the same
button.
buttons. Also, set/unset the