CAST ZFP Analogue Addressable Fire Alarm Panel
8.5.13

Show System Details

Enter AL3 (4444) > Engineering Functions > Show System Details.
This function lists system details including:
panel bootloader version number
main module and loop driver firmware version numbers
internal SD memory card information
number of A-Bus devices fitted
node name and site data version
Note: The information displayed will assist C-TEC Technical Dept. (available @ www.c-tec.com) to identify
the cause of any problems.
8.5.14

Safe Mode

Enter AL3 (4444) > Engineering Functions > Safe Mode.
This function disables all of the panel outputs whilst tests are being performed on the system. When selected
you will be asked to enter the five-digit safe mode password and safe mode time period.
Note: The default password is:
8.5.15

Clean Start

CAUTION: This function is for trained engineers only. Performing a clean start
COMPLETELY ERASES the panel's memory held on the internal SD memory card. Use with
extreme care. Ensure a system config download is retrieved BEFORE performing a clean start.
Enter AL3 (4444) > Engineering Functions > Clean Start.
This function allows engineers only to clear the panel's memory back to its factory default settings.
When selected, you will be asked to enter the five-digit security code.
8.5.16

Sync Network Data

These function only applies to networked panels.
Page 41 of 60  Approved Document No. DFU5030000 Rev 4  Installation and Programming Manual
12345.
Note: The default code is:
32767