CAST ZFP Analogue Addressable Fire Alarm Panel
8.3

Access Level 3 Menu Structure

Fig.17 shows the menu options available at access level 3.
Three 'access levels' are available at the panel; general user (access level 1), authorised user (access level 2)
and authorised systems engineer (access level 3). This manual focuses on the programming functions available
at access level 3 only; access levels 1 & 2 are covered in the separate User Manual (DFU5030050), including
information on how fire, fault, disablements and test conditions are reported and dealt with.
At access level 3, you can:
View any active fires, faults, disablements or test conditions that are displayed on the touchscreen.
Gain entry to the panel's access level 2 menu options.
Gain access to a wide range of engineering functions (see section 8.5) and commissioning functions (see section 8.6).
View and reset the panel's alarm counter (see separate User Manual DFU5030050 for details).
Display, filter or clear the panel's event log (see section 8.7).
Enable or disable zones, Input Groups, Output Groups and loop devices (see section 8.8).
Set the panel's time and date (see section 8.9).
8.4

How to Enter Access Level 3 (AL3)

Entry to AL3 using the panel's touchscreen
With the panel operating under normal conditions (shown below left), press the
touchscreen to show the access level 1 menu options (shown below right).
Using the touchscreen's numeric keypad, enter the four-digit access level 3 code. The default code is:
When the code has been entered correctly, the access level 3 menu options are displayed (shown below right).
Note that the panel will automatically exit access level 3 after 20 minutes without a button press.
Entry to AL3 using the panel's keyswitch and touchscreen
With the panel operating under normal conditions, turn the panel's keyswitch anticlockwise to the horizontal
position to display the access level 2 menu options. As detailed above, press the
input the four-digit access level 3 code.
Installation and Programming Manual  Approved Document No. DFU5030000 Rev 4  Page 32 of 60
Press the
button and the display shown below left appears.
button on the panel's
4444
.
button and