CAST ZFP Analogue Addressable Fire Alarm Panel
6.3

Z15 Sounder PCB Features

Feature
A-Bus PCB (Z15):
Cabling:
Protocol:
Powered from:
No. of Sounder Circuits:
Installation:
Number of PCBs:
PCB size (mm):
Common features:
Sounder PCB (Z15)
features:
(shown below)
Page 23 of 60  Approved Document No. DFU5030000 Rev 4  Installation and Programming Manual
Details
CAST ZFP 4-way Conventional Sounder PCB (full size). Part No. Z15.
2 core screened cable (plus 2 core for power).
RS485, 19200 BAUD, 8 Data, no Parity, 1 stop bit.
Note: We recommend an Aux EN 54-4/A2 PSU (external to the CAST ZFP panel – not supplied).
The PCB terminal labelled 'Ex' is used to report a fault from the Aux PSU. It is triggered from
an active IO signal from an open collector (O/C), or volt-free (with 0V common) relay O/P.
4 x 1A Conventional sounder outputs. Programmable and monitored.
PCBs normally installed within a CAST ZFP panel but may be extended up to 1km for
non-EN 54-2 functions.
Connect up to 15 A-Bus PCBs per Main 1 or 2-Loop PCB.
67 w x 165 h x 17 d.
24V supply inputs.
A-Bus RS485 connections (B, A, 0) to Main 1 or 2-Loop PCB.
Comms connections (PL4/PL5); Power In/Power Out connections (PL2/PL3).
15 available addresses (set using DIP switch SW1, see section 6.2).
Isolated RS485 multi drop.
LED indication for polling and power.
Standard 5mm fixed PCB connectors, accept up to 2.5mm
Common features (as above).
4 x 1A Monitored, conventional sounder circuits.
Each sounder output is programmable using CAST ZFP Programming Tools.
Note: The Z15 DOES NOT have the facility to 'pulse sounders'.
Separate LED indication provided for each sounder circuit.
2
cable.