Appendix 5 - Eacie Panel Technical Specification - C-TEC EACIE Installation, Maintenance & Operating Manual

Evacuation alert control and indicating equipment
Hide thumbs Also See for EACIE:
Table of Contents

Advertisement

EACIE Evacuation Alert Control and Indicating Equipment
Appendix 5 – EACIE Panel Technical Specification
EACIE Panel Part Numbers
EAP1/8/CA/CHASSIS
EAP2/8/CA/CHASSIS
EAP4/16/CA/CHASSIS
EAP4/24/CA/CHASSIS
EAP4/32/CA/CHASSIS
EAP4/40/CA/CHASSIS
EAP4/48/CA/CHASSIS
EAPBOX
Approvals / Certifications
Compliant with:
Power Supply, Charger and Batteries
Mains supply operating voltage:
Mains rated current:
Internal power supply:
Total output current limited to:
Battery charge capacity:
Maximum battery size and type:
Battery standby time:
Power rating:
Max. internal battery resistance 'Ri max':
Maximum power output voltage 'V max':
Minimum power output voltage 'V min':
Output ripple voltage (peak-to-peak):
EACIE panel quiescent currents:
Mains supply/battery charger monitored for
failure:
Batteries monitored for disconnection and
failure:
Earth fault monitoring:
Loop Driver Specification (programmable & monitored)
Number of loops:
Loop driver PCB types:
Max. output current per loop:
Communication Protocol:
Max. cable length per loop:
Cable type:
Max. allowable loop impedance (each
conductor):
Max. cable capacitance:
Auto-polling from each loop end:
Line monitored for o/c and s/c faults:
Relay Output (programmable)
Relay type:
Fuses (compliant to IEC EN60127 Pt2)
Primary fuse (F1):
Battery fuse (F2):
Communication Buses
Pager / DECT or IoT/BMS interface:
Diagnostics or IoT/BMS interface:
Programming PC interface:
Network
Network connection:
Max. number of Evacuation Alert Zones:
Indicators and Controls
User indicators (Switch Module):
User controls (Switch Module):
User indicators (Status Panel):
User controls (Status Panel):
Maintenance indicators:
Installation and Programming Manual  Approved Document No. DFU5030020 Rev 1  Page 36 of 38
8 Zone 1 Loop EVAC-ALERT Panel Chassis ONLY c/w 5A PSU, CAST Protocol. Requires EAPBOX.
8 Zone 2 Loop EVAC-ALERT Panel Chassis ONLY c/w 5A PSU, CAST Protocol. Requires EAPBOX.
16 Zone, 4 Loop EVAC-ALERT Panel Chassis ONLY c/w 5A PSU, CAST Protocol. Requires EAPBOX.
24 Zone, 4 Loop EVAC-ALERT Panel Chassis ONLY c/w 5A PSU, CAST Protocol. Requires EAPBOX.
32 Zone, 4 Loop EVAC-ALERT Panel Chassis ONLY c/w 5A PSU, CAST Protocol. Requires EAPBOX.
40 Zone, 4 Loop EVAC-ALERT Panel Chassis ONLY c/w 5A PSU, CAST Protocol. Requires EAPBOX.
48 Zone, 4 Loop EVAC-ALERT Panel Chassis ONLY c/w 5A PSU, CAST Protocol. Requires EAPBOX.
EVAC-ALERT Panel Cabinet to house 1 x EAP chassis. Custom FRS area specific 'N' security key required.
Evacuation Alert Panel designed to meet BS 8629.
PSU certified to EN54-4/A2.
230V
50/60Hz
1.3A r.m.s.
27.3Vdc ±1% nominal @ 20°C
5A @ 230Vac (4A with 1A battery charging)
7Ah min to 22Ah max.
2 x 12V, up to 22Ah capacity VRLA connected in series. YUASA REC22-12I batteries are recommended.
72 hours plus 30 minutes in alarm (the standby time of 72 hours is dependent on the system specification –
see BS 8629)
'I max a' = 4A; 'I max b' = 5A; 'I min' = 0mA
600mΩ
30V
20V ± 2% with mains On; 21V ± 2% with mains Off
≤ 320mV over the full input and output range of the PSU
1 loop variant = 110mA; 2 loop variant = 120mA; 4 loop variant = 130mA.
Refer to C-TEC's EACIE panel battery calculator tools for details.
 Yes
 Yes
 Yes
1, 2 or 4 (model dependent).
1 loop variant - fixed.
2 loop variant - may be extended to 4 loops plus optional network card.
4 loop variant - optional network card.
Main 1, 2 or 4-loop PCB
450mA (40V max.) per loop
C-TEC's CAST
1km
2-core screened, enhanced fire-resistant cable, min. size 1mm
wiring to sounders in flats.
20 ohm
.27µF
 Yes
 Yes
1 x fail safe fault relay to alarm receiving centre (ARC). Volt-free, single-pole changeover.
Max. switch current 1A, Max. switch voltage 30Vdc.
Active when faults are present or on total power failure.
T 2 A H 230V, 20mm ceramic (T = Time Delay; H = High Breaking Capacity)
®
7.5A MINI
automotive blade fuse
1 x RS232 connector. Compatible with ESPA and C-TEC ENVISION cloud-based data management system.
2 x RS485 connector. Compatible with C-TEC's ENVISION cloud-based data management system.
Via galvanically isolated USB connector (provided on the Z41/CA Control/Display module)
RS485 Hi-NET high integrity multi-path network connection via optional ZHN Hi-NET card.
Up to 8 CAST ZFP panels. Max length between nodes = 1km.
Up to 48 on a standalone EACIE panel. Up to 200 on a shared EACIE panel system.
Next to toggle switches are individual Evacuation LED (Red) & Zone Fault LED (Yellow).
Individual toggle switches to activate/deactivate evacuation alert devices.
Power LED (Green), Power Fault (Yellow), General Fault (Yellow).
Silence Fault Sounder.
LCD Touchscreen, 4.3 inch, 480 x 272 pixel, 24 bit, 16M RGB colour, all relevant EN54 indicators plus 4