CAST ZFP Analogue Addressable Fire Alarm Panel
8.5.3

Show PSU Status

This function allows you to view important information regarding the state of the panel's PSU and its standby
battery supply.
Enter AL3 (4444) > Engineering Functions > Show PSU Status.
Note: The information displayed will assist C-TEC Technical Dept. (available @ www.c-tec.com) to identify
the cause of any problems.
8.5.4

Test Input Group

This function allows you to perform tests on the panel's Input Groups, e.g. simulate a manual call point input
to the panel to test the cause and effects.
Input Groups include detectors (smoke, heat, multi), MCPs, inputs of I/O units, panel keyswitches, inputs of A-
Bus PCBs, monitored inputs.
Enter AL3 (4444) > Engineering Functions press the
tested from the list of available groups. In the next window choose the type of test to be performed on the Input
Group including: NORM or TRIG test.
8.5.5

Test Output Group

This function allows you to perform tests on the panel's Output Groups.
Output Groups include loop sounders and conventional sounders, VADs, outputs of I/O units, outputs of A-Bus
PCBs, panel relays.
Enter AL3 (4444) > Engineering Functions press the
be tested from the list of available groups. In the next window choose the type of test to be performed on the
Output Group including: OFF, ON and PULSED test.
8.5.6

Walk Test

This function allows you to put one or more of the system's detection zones into walk test mode. When a zone
is in walk test mode, any detector / manual call point triggered on that zone will turn on all of the sounders that
are assigned to that zone for a brief period.
Enter AL3 (4444) > Engineering Functions press the
the type of test to be performed, e.g. Sounders Enabled, Turn LED ON when in Fire, etc.
After making a selection, press the
walk test mode by pressing the zone button(s). This toggles the zone's state between 'NORMAL' operation and
'ON TEST'.
Note: Any zones in test can be viewed (and cancelled) by pressing the yellow
line of the touchscreen. Any devices being tested will be listed on the touchscreen.
8.5.7

Clear All Tests

This function globally clears all active tests on the system. The button is greyed out when there are no tests on
the system.
Enter AL3 (4444) > Engineering Functions > Clear All Tests.
Installation and Programming Manual  Approved Document No. DFU5030000 Rev 4  Page 38 of 60
button and in the next window select the zone(s) you wish to put into
button and choose the Input Group to be
button and choose the Output Group to
button and in the next window choose