EACIE Evacuation Alert Control and Indicating Equipment
7.4.5

Find Loop Break

This function allows you to find and display where a break in the loop exists.
When the FIND LOOP BREAK prompt appears select a loop, then press Accept and the panel will initialize both
ends of the loop.
Assuming there is a break in the loop, the device LEDs on either side of the break will be lit. The panel display
will also identify the precise location of the loop break between devices 'X + Y'.
7.4.6

Change Access Level 2 (AL2) Code

This function is used to change the four-digit code needed to enter the panel's access level 2 menu options.
At Access Level 3 > Engineering Functions, press the
7.4.7

Change Access Level 3 (AL3) Code

This function is used to change the four-digit code needed to enter the panel's access level 3 menu options.
At Access Level 3 > Engineering Functions, press the
Use the touchscreen's numeric keypad buttons as detailed above in section 7.4.6.
7.4.8

Show System Details

This function lists system details including the panel's firmware version number and internal SD memory card
information.
7.4.9

Clean Start

This function allows you to clear the panel's memory back to its factory default settings. When selected, you
will be asked to enter the five-digit security code. The default code is
Installation and Programming Manual  Approved Document No. DFU5030020 Rev 1  Page 26 of 38
button and the window below appears:
Use the touchscreen's numeric keypad buttons to enter
the new access level 2 code. After the fourth digit has
been entered, the panel will request you confirm the new
code by re-entering it.
Enter the code again by pressing the buttons in the same
sequence. If the two codes match, the panel will accept the
code and you will be taken back to the engineering menus.
If you type an incorrect confirmation code you will be
prompted to start the new code entry sequence again.
button.
32767
CAUTION: This function is for trained engineers only.
Performing a clean start COMPLETELY ERASES the
panel's memory (held on the internal SD memory card).
.