Connections
3.4
Adjusting elements on technology board (see Fig. 3.2)
Resistors R135 and R136:
0Ω resistors as connection earth - ground M. M is connected to earth in the delivery state. These resistors should
be removed only for the purpose of preventing disturbance caused by earth loops, i.e. if the electronics ground is
connected to earth in some other way (e.g. via signal leads or to the ground of the power supply). The earth -
ground M connections on the other electronics boards must then also be separated (see description of basic
converter unit or of other option boards).
Plug-in jumpers:
Pin 1 of the plug-in jumpers has a screen-print marking. The distance between pin 2 and pin 3 on X1 and X5 is
slightly larger to prevent them from being linked in a meaningless connection. Examples:
Pin
1
2
3
Pin
X7
Plug-in jumper
Pin
designation
connection
X1
(X1-1)
1-2
(X1-2)
3-4
X2
(X2-1)
1-2
(X2-2)
3-4
X3
(X3-1)
1-2
(X3-2)
3-4
X4
(X4-1)
1-2
(X4-2)
3-4
X5
(X5-1)
1-2
(X5-2)
3-4
X6
1-2
2-3
X7
1-2
2-3
X8
1-2
2-3
X9
1-2
2-3
€ ó
X10
1-2
2-3
€ ó
X11
1-2
2-3
Table 3.3
Plug-in jumpers
The purpose of the bus terminator is to prevent line reflections at both ends of the bus cable. It must be
activated:
on both connected devices with a point-to-point connection
only on the devices connected at the start and end of the bus with a bus connection.
ó
Bus terminating resistors are soldered in at the transmit output of interface 2.
3-5
ENGLISH
1
2
3
4
X2
Deliv.
Function
state
Analog input 1: Current input
x
Analog input 1: Voltage input
Analog input 2: Current input
x
Analog input 2: Voltage input
Analog input 3: Current input
x
Analog input 3: Voltage input
Analog input 4: Current input
x
Analog input 4: Voltage input
Analog input 5: Current input
x
Analog input 5: Voltage input
Analog output 1: Current output
x
Analog output 1: Voltage output
Analog output 2: Current output
x
Analog output 2: Voltage output
Bus terminator for RS485 interface 1 on X132 activated. This
plug-in jumper must be set in the same way as jumper X9.
x
Bus terminator for RS485 interface 1 on X132 deactivated. This
plug-in jumper must be set in the same way as jumper X9.
Bus terminator for RS485 interface 1 on X132 activated. This
plug-in jumper must be set in the same way as jumper X8.
x
Bus terminator for RS485 interface 1 on X132 deactivated. This
plug-in jumper must be set in the same way as jumper X8.
Bus terminator on receive input of RS485 interface 2 on X133
activated. This plug-in jumper must be set in the same way as
jumper X11.
x
Bus terminator on receive input of RS485 interface 2 on X133
deactivated. This plug-in jumper must be set in the same way as
jumper X11.
Bus terminator for RS485 interface 2 on X133 activated. This
plug-in jumper must be set in the same way as jumper X10.
x
Bus terminator for RS485 interface 2 on X133 deactivated. This
plug-in jumper must be set in the same way as jumper X10.
Siemens AG
6SE7080-0CX87-0BB0
T100 Technology Board
Operating Instructions
01.00