4.4.2 Repair procedures

To remove the expansion valve coil
Service manual
86
Is the flow through the expansion valve
correct?
Yes
No
After all checking procedures listed above have been performed:
Is the problem solved?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 If needed, remove any parts or insulation to create more space for the
removal.
2 Pull up the expansion valve coil to remove it from the expansion valve body.
INFORMATION
It may be needed to turn the expansion valve coil 1/8 turn counter clockwise to
unlock it. Make sure to note the correct orientation (position) of the expansion valve
coil before removal.
A
A Class 20~35 unit
a Expansion valve coil
b Expansion valve coil harness
Action
Component is OK. Return to the
troubleshooting of the specific error
and continue with the next step.
Replace the expansion valve, see
"4.4.2 Repair
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
a
b
4
procedures" [
 86].
4
"4.14 Plate
work" [
 144].
RXJ20~50A + FTXJ-A(W)(S)(B)
Split Emura 3 R32
ESIE22-04B – 2022.08