To remove the swing flap motor gearcase assembly
Service manual
166
INFORMATION
To replace the motor, the complete gearcase assembly MUST be replaced. This
includes the secondary swing flap motor, swing raster motor and gears.
As the secondary swing flap motor wiring harness is the same harness as the main
swing flap motor wiring harness, see
wiring harness.
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Remove the switch box, see
2 Remove the main swing flap from the indoor unit (by clicking it out).
3 Remove the secondary swing flap from the indoor unit (by clicking it out).
4 Remove the right side fan guard from the indoor unit (by clicking it out).
c
a Fan guard
b Swing raster motor rod
c Swing raster
5 Put a small drain pan (or container) under the drain hose.
6 Remove the screw from the fixation bracket and pull the drain hose
downwards to remove it from the indoor unit.
7 Remove the 3 screws from the swing flap motor gear case assembly. Do NOT
yet remove the assembly from the indoor unit.
a
"Repair
"4.14 Plate
work" [
b
a
b
a
4
procedures"  [
  163] to replace the
4
"4.14 Plate
work" [
 144].
4
 144].
a
RXJ20~50A + FTXJ-A(W)(S)(B)
Split Emura 3 R32
ESIE22-04B – 2022.08