6
|
Maintenance
6.7 To clean the titanium apatite deodorising filter and the silver
particle filter (Ag-ion filter)
Service manual
196
INFORMATION
If the dust does NOT come off easily, wash the air filters with a neutral detergent
diluted in lukewarm water. Dry the air filters in the shade.
Be sure to remove the titanium apatite deodorising and silver particle filters.
It is recommended to clean the air filters every 2 weeks.
Is the problem solved?
Yes
No
INFORMATION
Clean the filter with water every 6 months.
1 Remove titanium apatite deodorising filter and the silver allergen removal air
purifying filter from all 4 claws.
a Claw
2 Remove the dust from the filter with a vacuum cleaner.
3 Soak the filter for 10 to 15 minutes in warm water.
Note: Do NOT remove the filter from the frame.
4 After washing, shake off remaining water and dry the filter in the shade. Do
NOT wring out the filter when removing water.
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.