Daikin Emura RXJ20A5V1B Service Manual page 162

Split 3 r32
Hide thumbs Also See for Emura RXJ20A5V1B:
Table of Contents

Advertisement

4
|
Components
Service manual
162
Pins
5-1
5-2
5-3
5-4
4-1
4-2
4-3
3-1
3-2
2-1
Swing flap motor resistance
measurements are correct?
Yes
No
3 Remove the swing flap motor, see
4 Measure the resistance between the following pins of the connector on the
swing flap motor.
Result: The measurements MUST be as shown in the table below.
Pins
1-2
1-3
1-4
1-5
2-3
2-4
2-5
3-4
3-5
4-5
Swing flap motor resistance
measurements are correct?
Yes
No
Measured resistance (Ω)
353.4~406.6
706.8~813.2
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Continue with the next step.
4
"Repair
procedures" [
 166].
Measured resistance (Ω)
353.4~406.6
706.8~813.2
Action
Replace the swing flap motor wiring
harness, see
"Repair
4
procedures" [
 163].
Replace the swing flap motor, see
"Repair
procedures" [
4
 163].
RXJ20~50A + FTXJ-A(W)(S)(B)
Split Emura 3 R32
ESIE22-04B – 2022.08