Indoor Unit Fan Motor; Checking Procedures - Daikin Emura RXJ20A5V1B Service Manual

Split 3 r32
Hide thumbs Also See for Emura RXJ20A5V1B:
Table of Contents

Advertisement

4.8 Indoor unit fan motor

4.8.1 Checking procedures

To perform a mechanical check of the DC fan motor assembly
To perform an electrical check of the DC fan motor assembly
RXJ20~50A + FTXJ-A(W)(S)(B)
Split Emura 3 R32
ESIE22-04B – 2022.08
Is the problem solved?
No
INFORMATION
It is recommended to perform the checks in the listed order.
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Check the fan for damage, deformations and cracks. Replace the fan as
needed.
2 Check that the fan is correctly installed on the DC fan motor. Correct as
needed.
3 Manually rotate the fan and check the friction of the DC fan motor shaft
bearing.
Is the DC fan motor shaft friction
normal?
Yes
No
Prerequisite: First perform a mechanical check of the DC fan motor assembly, see
"4.8.1 Checking
procedures" [
1 Remove the cover from the switch box; see
2 Disconnect the DC fan motor connector from the appropriate PCB.
3 Measure the resistance between the pins 1-2, 1-3, and 2-3 of the DC fan
motor connector.
Result: All measurements MUST be approximately the same.
DC fan motor measurements are
correct?
Yes
No
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
"4.14 Plate
Action
Perform an electrical check of the DC
fan motor assembly, see
"4.8.1 Checking
Replace the DC fan motor assembly, see
"4.8.2 Repair
4
 101].
"4.14 Plate
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Replace the DC fan motor, see
"4.8.2 Repair
4
Components
|
4
work" [
 144].
4
procedures" [
 101].
4
procedures" [
 102].
4
work" [
 144].
4
procedures" [
 102].
Service manual