Input Wiring Example - Mitsubishi Electric MELSEC iQ-F Series Training Manual

Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

Input wiring example

Sink input [AC power supply type]
FX5U-32MT/ES
Input
impedance
5V 0V 24V
FX5-16EX/ES
5V 0V 24V
FX5-16EX/ES
5V 0V 24V
*1 Handle the power supply circuit properly in accordance with "Power Supply Wiring."
*2 For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required.
*3 In the case of sink input wiring, short-circuit the [S/S] and [24V] terminals of the CPU module.
The service power supply or external power supply can be used for all inputs (X) of the CPU module. However
you need to select either one for each CPU module or I/O module. Both power supplies cannot be used
together in the same module.
L
Class D grounding
N
*3
S/S
0V
0V
24V
24V
X0
X1
Input
terminal
S/S
X0
X1
Input
terminal
S/S
X0
X1
Input
terminal
Fuse
*1
Three-wire
sensor
Two-wire
proximity
*2
sensor
24 V DC
Three-wire
sensor
12

Advertisement

Table of Contents
loading