Overview
6-1-2 Hold/Clear for I/O Memory Data
Name
Input Area
IR 000
Output Area
IR 001
Work Area
IR 002 to
IR 049,
IR 200 to
IR 219
SR Area
SR 220 to
SR 255
AR Area
AR 00 to
AR 27
LR Area
LR 00 to
LR 31
Timer Completion
TIM/CNT 000
Flags
to TIM/CNT
255
Timer PVs
TIM/CNT 000
to TIM/CNT
255
Counter Completion
TIM/CNT 000
Flags
to TIM/CNT
255
Counter PVs
TIM/CNT 000
to TIM/CNT
255
DM Area
General-
DM 0000 to
purpose
DM 6143
read/write
words
General-
DM 6200 to
purpose
DM 6599
read-only
words
Error Log
DM 6144 to
Area
DM 6199
Unit Setup
DM 6600 to
Area
DM 6655
EM Area
EM 0000 to
EM 2047
66
The following table shows when the status of the memory areas is held and
when it is cleared.
Addresses
External I/O
allocation
lloc tion
Yes
Yes
No
No
No
No
No
No
No
No
No
No
Note
1. "Operating mode changed" means between RUN or MONITOR mode and
PROGRAM mode.
2. The status of Timer Completion Flags and Timer PVs is held when the oper-
ating mode changes from RUN mode or MONITOR mode to PROGRAM
mode, but it is cleared when the operating mode is changed from PRO-
GRAM mode to RUN mode or MONITOR mode.
3. It is possible to set whether data in the EM Area is held or cleared in the Unit
Setup Area (bits 12 to 15 in DM 6600).
4. With the Customizable Counter Unit, there is no function (e.g., such as an
IOM Hold Bit) for holding the bit status in the cleared areas above when the
operating mode is changed or the power supply is turned ON.
Fatal errors
Operating
mode
mode
FALS error
changed
(See note 1.)
Cleared
Held
Cleared
Cleared
Cleared
Held
(Refer to the individual explanations for the functions.)
Held or cleared depending on the address.
Cleared
Held
Held
Held
(See note 1.)
Held
Held
(See note 2.)
Held
Held
Held
Held
Held
Held
According to
According to
setting.
setting.
(See note 3.)
(See note 3.)
Section
Power
s pply
supply
Other fatal
turned ON
errors
Cleared
Cleared
Cleared
Cleared
Cleared
Cleared
Cleared
Cleared
Held
Cleared
Held
Cleared
Held
Cleared
Held
Held
Held
Held
According to
According to
setting.
setting.
(See note 3.)
(See note 3.)
6-1