Omron Sysmac CS1 Operation Manual page 152

Customizable counter units
Hide thumbs Also See for Sysmac CS1:
Table of Contents

Advertisement

Troubleshooting Tables
Error
Error
Unit indicators
RUN
OPN
ERC
No END
Lit
OFF
Lit
Unit
Lit
OFF
Lit
system
error
(FALS)
Unit cycle
Lit
OFF
Lit
time
monitor
error
CPU Errors Resulting in Customizable Counter Unit Fatal Errors
Unit indicators
Error
RUN
OPN
ERC
Unit
OFF
OFF
Lit
recognition
error
Unit not
OFF
OFF
OFF
recognized
Unit
OFF
OFF
OFF
number
error
Unit setting
OFF
OFF
OFF
read error
Bus error
OFF
OFF
OFF
132
Error
Error
Error log
Error log
message
message
(SIOU code,
(SIOU code,
details 1,
details 1,
ERH
details 2)
details 2)
OFF
NO END
0360 Hex
INST
00 Hex
F0 Hex
OFF
SYS FAIL
0360 Hex
FALS**
00 Hex
FALS No. (1
to 99 BCD)
OFF
SYS FAIL
0360 Hex
FALS9F
00 Hex
F9 Hex
Error
Error log
message
me
age
(SIOU code,
(SIOU code,
details 1,
ERH
details 2)
Lit
---
---
Lit
---
0006 Hex
08 Hex
00 Hex
Lit
---
---
Lit
---
---
Lit
---
---
SR 23500
SR 23500
Error
Error
Meaning and corrective measures
Meaning and corrective measures
to
to
flags
flags
SR 23507
SR 23507
F0 Hex
SR 23511 END(01) is not written anywhere in
program.
Write END(01) at the final address of
the program.
FALS No.
SR 23511 An FALS(07) instruction has been
(1 to 99
executed in the program.
BCD)
Check the FALS number to determine
the conditions that would cause
execution, correct the cause, and
clear the error.
F9 Hex
SR 23511 The cycle time has exceeded the
FALS 9F Cycle Time Monitoring Time
(DM 6618).
Check the cycle time and adjust the
Cycle Time Monitoring Time if
necessary.
SR 23500
Error
Meaning and corrective measures
to
to
flag
flags
SR 23507
---
---
The Customizable Counter Unit is not
recognized as a Special I/O Unit by
the CPU Unit.
Try to power-up again.
---
---
The actual I/O tables do not agree
with the registered I/O tables.
Recreate the I/O tables in the CPU
Unit.
---
---
The unit number is not set correctly
or the same number has been set for
another Unit.
Correct the unit numbers and try to
power-up again.
---
---
No response to a FINS command or
CPU settings could not be read.
Try to power-up again.
---
---
The access right could not be
obtained.
Try to power-up again.
Section
9-3