Omron Sysmac CS1 Operation Manual page 79

Customizable counter units
Hide thumbs Also See for Sysmac CS1:
Table of Contents

Advertisement

Unit Setup Area
Settings Enabled whenever Changed
Address
Bits
DM 6650
00 to 03
Communications settings for peripheral port
04 to 15
(Reserved by system.)
DM 6651
00 to 07
Peripheral port baud rate
Note: This setting is valid when connected to
the CX-Programmer via peripheral bus. The
baud rate setting must agree with the baud
rate set for the CX-Programmer.
08 to 15
(Reserved by system.)
DM 6652
00 to 15
(Reserved by system.)
to
DM 6654
DM 6655
00 to 03
Error log storage method
04 to 07
(Reserved by system.)
08 to 11
Cycle time exceeded (10 ms) detection
12 to 15
(Reserved by system.)
Function
Contents
0 Hex: Standard settings (baud rate: 9,600
bps; data length: 7 bits; 1 start bit; 2 stop bits;
even parity).
1 Hex: Communications settings are
determined by the setting of DM 6651.
If the setting of bits 00 to 03 in word m+6
(Communications Settings for Peripheral Port)
of the DM Area memory is 1 Hex (standard
settings), the setting of DM 6651 will be
ignored.
Note: The Customizable Counter Unit
automatically recognizes the following and
switches to the appropriate serial
communications mode:
• Connection to a Programming Console (Pro-
gramming Console bus)
• Peripheral bus
---
00 Hex: 1,200 bps
01 Hex: 2,400 bps
02 Hex: 4,800 bps
03 Hex: 9,600 bps
04 Hex: 19,200 bps
---
---
0 Hex: Shift (The oldest entries are deleted.)
1 Hex: Don't shift (New errors are ignored.)
---
0 Hex: Detected
1 Hex: Not detected
Note: If detection is enabled, when a cycle
time overrun is detected, bit SR 23509 turns
ON.
---
Section
5-1
59