Omron Sysmac CS1 Operation Manual page 82

Customizable counter units
Hide thumbs Also See for Sysmac CS1:
Table of Contents

Advertisement

Unit Setup Area
Settings for Analog Outputs (CS1W-HCA22 Only)
Address
Bits
DM 6613
00 to 07
Analog output 1
08 to 15
DM 6614
00 to 07
Analog output 2
08 to 15
Address
Bits
DM 6630
00 to 07
For both analog
outputs 1 and 2
08 to 15
(Reserved by
system.)
DM 6631
00 to 15
For both analog
outputs 1 and 2
DM 6632
00 to 15
(Reserved by
to
system.)
DM 6643
62
Settings Enabled at Startup
Function
Output signal range
Operation when output turned OFF
g
Output signal range
Operation when output turned OFF
Settings Enabled at Startup and when Operation Starts
Function
Analog output
method
---
Adjustment mode
password
---
Details
00 Hex: –10 to 10 V
01 Hex: 0 to 10 V
02 Hex: 1 to 5 V
03 Hex: 0 to 5 V
5A Hex: Output disabled (See note.)
Note: Setting 5A can be used to
shorten the I/O refresh time.
00 Hex: Cleared
01 Hex: Held
02 Hex: Peak value
Same as for analog output 1.
Details
00 Hex: END refresh (The values stored in AR 14
and AR 15 are output as analog signals after
execution of the END instruction.)
01 Hex: Immediate refresh using instructions
(Analog signal output with execution of SPED or
ACC instruction. Output values are stored in AR 14
and AR 15 for monitoring.)
5A5A Hex: Adjustment mode enabled
Setting other than 5A5A: Adjustment mode
disabled