Profibus Address - Siemens SIMOTION ADI4 Equipment Manual

Analog drive interface for 4 axes
Hide thumbs Also See for SIMOTION ADI4:
Table of Contents

Advertisement

Parameter assignment
4.4 PROFIBUS parameters
4.4.2

PROFIBUS address

Procedure
Inserting an ADI4 DP slave into the configuration will open the "Properties - PROFIBUS Interface
ADI4" dialog, "Parameters" tab:
Figure 4-1
The displayed address value was automatically set by HW Config to the next available PROFIBUS
address within the configuration.
Note
The PROFIBUS address of the ADI4 DP slave can be set to any value, in principle. However, it must
be ensured that the PROFIBUS address setting in HW Config matches the DIP switch setting on
the ADI4 DP slave:
There is no automatic adjustment!
The following data must agree:
• SIMATIC S7 configuration ADI4 DP slave
PROFIBUS address
• ADI4 module DIP switch S2
PROFIBUS address
44
PROFIBUS address
SIMOTION ADI4 - Analog Drive Interface for 4 Axes
Equipment Manual, 07/2017, A5E33446849B

Advertisement

Table of Contents
loading

Table of Contents