Digital inputs
If the digital inputs are not supplied with the internal supply voltage of X6-2, Pin 1 (P24OUT), this
supply voltage can optionally be replaced with an external power source (+24 VDC, 1 A
maximum).
The reference ground (GND) of the external power supply source must be connected with X6-2,
Pin 12. X6-2, Pin 1 (P24OUT) remains open.
Specification of the supply voltages (+24 VDC)
The external supply voltages for the ADI4 module, the digital outputs, and optionally the digital
inputs must comply with the specifications provided in the "Encoder supply voltages" table.
Table 3-15
Voltage
Ripple
Current load
Power consumption
P24EXT1: Supply voltage of the ADI4 module
1)
P24EXT2: Supply voltage for the digital outputs
P24OUText: Optional supply voltage for the digital inputs
NOTICE
External supply voltage
The external supply voltages must each be generated as functional extra-low voltage with safe
electrical isolation (DIN EN 60204-1, PELV).
SIMOTION ADI4 - Analog Drive Interface for 4 Axes
Equipment Manual, 07/2017, A5E33446849B
Specification of the external supply voltages
Supply voltage
Minimum
Nominal
Maximum
Maximum
Typical
Maximum
Typical
Maximum
1)
P24EXT1
0.5 A
1 A
12 W
30.2 W
Hardware description
3.4 Power supply
P24EXT2
P24OUText
18.5 V
24 V
30.2 V
3.6 V
pp
-
8 A
-
241.6 W
0.1 A
1 A
3.02 W
30.2 W