Overview; Unit Number - Omron SYSMAC CS1W-RPT01 Operation Manual

Controller link units
Hide thumbs Also See for SYSMAC CS1W-RPT01:
Table of Contents

Advertisement

CJ-series Controller Link Units
4-2-1

Overview

CLK21-V1
RUN
ERC
INS
SD
TER
ERH M/A LNK RD
UNIT
4
No.
NODE
No.
1
x10
0
x10
ON
1
BAUD
SW1
RATE
2
TER SW
ON
BD H
BD L
SHLD
4-2-2

Unit Number

Note
92
UNIT
4
No.
NODE
No.
1
x10
0
x10
ON
1
BAUD
SW1
RATE
2
Set the unit number for each Unit using the rotary switches on the front of the
Unit. The unit number is used to identify a CPU Bus Unit within the PLC. Any
unit number can be set between 0 and F in hexadecimal (00 to 15 in decimal).
Item
Setting method
Setting range
Node
Set the node address using a small flat-blade screwdriver, being careful not to
damage the rotary switches.
1. Always turn OFF the PLC's power before setting the unit number.
2. When setting a Unit for the first time or changing the existing setting, create
a I/O table in the PLC's CPU Unit.
3. Do not set the same unit number twice within the same PLC. An error will
occur if the same unit number is set for two different Unit, and the CPU Unit
will not be able to recognize the Units.
4. When the Unit is recognized by the PLC's CPU Unit, "NS" will be shown in
the I/O table displayed for the CX-Programmer programming device.
Unit Number
Setting range
01 to F (default is 0)
Node Address
Setting range
01 to 32 (default is 01)
Baud Rate
Pins
Baud rate
Pin 1
Pin 2
OFF
OFF
2 Mbps
ON
OFF
1 Mbps
OFF
ON
500 Kbps
ON
ON
Cannot be set.
Note
Factory default setting is in bold.
Terminating Resistance
Front switch
Terminating
resistance
OFF
Not connected
(factory default)
ON
Connected
UNIT
4
Note: The factory default settings are shown.
No.
Single-digit hexadecimal
0 to F (decimal 00 to 15, default is 0)
All nodes in the Network
Section 4-2
Nodes
All nodes in the Network
Nodes
All nodes in the Network
Maximum
Nodes
transmission
distance
500 m
Set same
rate for all
800 m
nodes in the
1 km
Network.
Nodes
All nodes in the Network
Turn ON the terminating resis-
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.
Specifications