Cleaning and Inspection

Error message
Node XX Node size
Warning: The total node send
and receive size of ** exceeds
12000
Total Node send size of **
exceeds max 20000
Total Node send size of **
exceeds max 8000
Total Node send size of **
exceeds max 62000
Total Node send size is 0
Total Node send size of **
exceeds max 1000
Total Node send size of **
exceeds max 4000
Node XX Area Overlap
Warning: Duplicated area exists
Node XX Area Conflict
in Area 1 and status area
Warning: Duplicated area exists
in Area 2 and status area
Warning: Link memory areas 1
and 2 are both set to - [Area]
Link memory areas 1 and 2 are
both set to [Area]
Link memory areas 1 and 2 are
both set to [Area]
9-5
Cleaning and Inspection
320
The total number of send and receive words exceeds
12,000. Controller Link Units with unit version 1.2 or later are
required for data links with 20,000 send and receive words.
For pre-Ver. 1.2 Controller Link Units, reduce the number of
send and receive words.
The total number of send and receive words exceeds
20,000. Reduce the number of send and receive words to
within the maximum.
The total number of send and receive words exceeds 8,000.
Reduce the number of send and receive words to within the
maximum.
The total number of send and receive words exceeds
62,000. Reduce the number of send and receive words to
within the maximum. (The 62,000 maximum can be
exceeded by personal computer boards only.)
The number of allocated words for node ** in node No. xx is
0. Change the number of words or delete the node.
The total number of send words for node XX exceeds 1,000.
Set the number of send words to 1,000 words or less.
The total number of send words for node XX exceeds 4,000.
Set the number of send words to 4,000 or less, or to 1,000 or
less. (More than 1,000 send words can be set for the CS1W-
CLK23 and CJ1W-CLK23.)
The same words have been allocated for both the Data Link
Area 1 and status area. If the duplication is not intended,
change the settings for either area. If the duplication is
intended, the data link tables can be transmitted without
making any changes.
The same words have been allocated for both the Data Link
Area 2 and status area. If the duplication is not intended,
change the settings for either area. If the duplication is
intended, the data link tables can be transmitted without
making any changes.
The same area has been set for both Data Link Area 1 and
2. The same area can be set if using Controller Link Units
with unit Ver. 1.2 or later. If a pre-Ver. 1.2 Controller Link Unit
is being used, set a different area each for Area 1 and Area
2. (This message is displayed for CS/CJ-series CPU Units
only.)
The same area has been set for both Data Link Area 1 and
2. Set a different area each for Area 1 and Area 2. (This mes-
sage is displayed for CS/CJ-series CPU Units only.)
The same address has been set for the Data Link Area and
the area in which both Area 1 and Area 2 are set. Reset the
addresses so that no duplication occurs. (This message is
displayed for CS/CJ-series CPU Units only.)
The
symbol refers to the corresponding node address. The two
XX
asterisks (**) refer to the corresponding area type, address, and number of
words.
This section describes cleaning and inspection procedures that are to be per-
formed as daily maintenance.
Section 9-5
Troubleshooting