Specifications and Configurations
Long-distance Wiring
Wired Controller Link Unit
Twisted-pair cable
500 m max.
(See note.)
Converting Part of the Transmission Line to Optical Fiber
Wired Controller Link Unit
Twisted-pair cable
Optical cable (H-PCF or GI)
Two Repeater Units of the same model must be used when part of the trans-
mission line uses optical fiber.
Maximum Configuration of 62 Nodes
Wired Controller Link Unit
Twisted-pair cable
32 nodes max.
The following Controller Link Units/Support Boards must be used to construct
a network with more than 32 nodes:
CS1W-RPT01
Repeater Units
Twisted-pair
cable
500 m max.
(See note.)
Twisted-pair cable
500 m max. (See note.)
CS1W-RPT02 or
CS1W-RPT03
Repeater Units
Twisted-pair cable
Section 1-2
Wired Controller Link Unit
Note: At 2 Mbit/s
Wired Controller Link Unit
CS1W-RPT01
Repeater Unit
Wired Controller Link Unit
Twisted-pair cable
32 nodes max.
13