Specifications and Configurations
1-2-6

Programming Devices

Programming Device for the PLC
Note
Note Normally, the communications cable must be disconnected from a Wired Con-
troller Link Unit to replace it. Doing this, however, will interrupt communica-
tions on the network, requiring that all node be turned OFF to ensure safety
before replacing a Unit. With the above Relay Terminal Block, a Controller
Link Unit can be replaced by turning OFF only the specific Unit being
replaced, i.e., without turning OFF any other Units. The communications
cables are left connected to the Relay Terminal Block and only the Relay Ter-
minal Block is removed from the Controller Link Unit. (The built-in terminating
resistance connected at the Units at the end of the network prevents using the
Relay Terminal Block on the end Units.) Refer to Appendix C Using the Relay
Terminal Block for details on using the Terminal Relay Block.
A Programming Device for the PLC, the Controller Link Support Software, or
CX-Programmer are needed to use a Controller Link Network.
One of the following Programming Devices is necessary when using the auto-
matically setting data links or the message service.
Programming
Console
IBM PC/AT or
compatible
The following operations are possible.
• Selecting manual or automatic setting for data links.
• Setting the data link mode to "automatic" (software switch setting).
• Starting/stopping data links (Start Bit: ON/OFF)
• Programming for the message service.
• Reading (monitoring) the network status.
Programming
Device
CX-Programmer
(for PLC)
Programming
Console
1. Use the CX-Net in CX-Programmer version 5.0 or higher to set data link
send and receive areas that exceed 12,000 words, and to set data link ta-
bles that allocate the same area for Area 1 and Area 2.
Start-up node
or
+
CX-Programmer
Software switches (DM Area)
External
Model
appearance
WS02-CXPC
@
V
CQM1-PRO01-E
C200H-PRO27-E
CVM1-PRS21-EV1
Section 1-2
CPU Unit
Controller Link
Applicable PLCs
@
CS/CJ-series,
-E-
C200HX/HG/HE,
CVM1-series, and
CQM1H-series PLCs
C200HX/HG/HE,
C200H/C200HS,
CQM1, and
CQM1H-series PLCs
CVM1 and
CV-series PLCs
23