Setting The Unit After Replacement - Omron SYSMAC CS1W-RPT01 Operation Manual

Controller link units
Hide thumbs Also See for SYSMAC CS1W-RPT01:
Table of Contents

Advertisement

Handling Precautions
9-6-2

Setting the Unit after Replacement

!Caution After replacing the CPU Unit, transfer important data, such as DM and HR
Resetting Network Parameters
1,2,3...
CS/CJ-series Controller Link Units
DM 30000 + 100 × n
n = Unit number
C200HX/HG/HE Controller Link Units
Operating level 0
DM 6400
CVM1 and CV-series Controller Link Units
DM 2000 + 100 × n
n = Unit number
parameter status to other nodes, so there is the chance that network pa-
rameters in the entire Network will be damaged.
After replacing a Controller Link Unit, reset the hardware switches, software
switches, and data link tables, and wire it in the same manner as the previous
Unit. This section describes settings that require particular care. Refer to the
Unit replacement methods later in this section for details on replacing the Unit.
Area contents, to the new CPU Unit before restarting operation. Depending
on the program, accidents can occur as a result of incorrect DM or HR Area
contents.
CS/CJ-series, CVM1, and CV-series Controller Link Units store data such as
data link tables, network parameters, and routing tables in the CPU Unit.
When replacing the CPU Unit, reset these settings using the Controller Link
Support Software.
When a C200HX/HG/HE or CQM1H-series Controller Link Unit has been
replaced or a CPU Unit has been replaced for a CS/CJ-series, CVM1, or CV-
series Controller Link Unit, it is necessary to reset the network parameters,
data link tables, and routing tables. This sections describes the resetting pro-
cedure for the network parameters. For details on data link table resetting pro-
cedures, refer to 5-2 Setting Data Links and for routing table resetting
procedures, refer to 7-4 Setting Routing Tables.
1. Network parameters are read from the polling node when the Network is
activated and this information is distributed to all nodes in the Network. For
this reason, set the polled/polling node setting in the DM Parameter Area
for the node replaced to a polled node before reconnecting the Unit to the
Network. For C200HX/HG/HE and CQM1H-series Controller Link Units,
the EEPROM Clear Bit in the DM Parameter Area will already be set to
clear EEPROM (ON or 1).
Polled node/polling node
Operating level 1
DM 6420
EEPROM Clear Bit
Polled node/polling node 0: Polling node
Polled node/polling node
– : Other settings
0: Polling node
1: Polled node
0: Do not clear EEPROM
1: Clear EEPROM
1: Polled node
– : Other settings
0: Polling node mode
1: Polled node
Section 9-6
–: Other settings
323