Commands and Responses for Controller Link Units

6-5-12 ERROR LOG CLEAR

Command Block
Response Block
214
Parameter
Response
Error log data (response): The specified error log records are returned in
sequence starting from the beginning record number. The total number of
bytes required is calculated as follows:
No. of records x 10 bytes
The configuration of each error record is as follows:
1st byte
Error code
Details
Error code, details: These parameters show the contents of errors. For
details, refer to 9-3-2 Error Codes.
Date and time: These parameters show the seconds, minutes, hour (0 to
23), date, month, and year (the rightmost two digits) in BCD specifying the
time that the error occurred.
Note
1. If the PLC does not have the specified number of records, all the records
that have been stored in the PLC up to the point that the command is exe-
cuted will be returned.
2. If there is no error log registered, a response code of 1103 (Hex) will be
returned.
Clears all error log records and sets the error log pointer to 0.
21
03
Command
format
21
03
Command
Response
format
code
Model
CS1W-CLK23
CJ1W-CLK23
Max. no. of
0040 hex, fixed
stored records
(Decimal: 64)
64 records max.
No. of stored
0001 to 0040 hex
records
(Decimal: 1 to 64)
No. of records
0001 to 0040 hex
(Decimal: 1 to 64)
Minute
Day Hour Year Month
Second
Section 6-5
CS1W-CLK21(-V1)
CJ1W-CLK21(-V1)
0027 hex, fixed
(Decimal: 39)
39 records max.
0001 to 0027 hex
(Decimal: 1 to 39)
0001 to 0027 hex
(Decimal: 1 to 39)
10th byte

Advertisement