Omron SYSMAC CS1W-RPT01 Operation Manual page 338

Controller link units
Hide thumbs Also See for SYSMAC CS1W-RPT01:
Table of Contents

Advertisement

Error Log
Error
Contents
code
0101
Transmission failed; local node
Hex
not in Network
0103
Transmission failed; retry count
Hex
exceeded
0104
Transmission failed; maximum
Hex
number of frames exceeded.
0105
Transmission failed; node
Hex
address incorrect
0106
Transmission failed; redundant
Hex
node address
0107
Transmission failed; destination
Hex
node not in Network
0108
Transmission failed; specified
Hex
Unit does not exist
Detail code
1st byte
2nd byte
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network
address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Correction
Written to
EEPROM
Refer to page 274
No
Troubleshooting
Using Indicators and
place the local node
into Network.
Using the Controller
No
Link Support Soft-
ware or FINS
commands, run
echoback test and
check operating envi-
ronment if errors
occur.
Reduce the number
No
of events per com-
munications cycle or
increase the maxi-
mum number of
network parameter
frames.
Refer to 4-2 CJ-
No
series Controller Link
Units or 4-4 CVM1
and CV-series Con-
troller Link Units and
check node address
settings to be sure
they are within range
and unique.
Correct node
No
addresses so that
they are unique
within the same
Network.
Refer to 9-1 Trouble-
No
shooting Using Indi-
cators and place
destination node into
Network.
Refer to 4-4 CVM1
No
and CV-series Con-
troller Link Units and
check unit address
and unit number of
destination.
Section 9-3
Applicable
PLC
All
All
All
All
All
All
All
313