Omron SYSMAC CS1W-RPT01 Operation Manual page 159

Controller link units
Hide thumbs Also See for SYSMAC CS1W-RPT01:
Table of Contents

Advertisement

Setting Data Links
DM 30000 + 100 × Controller Link Unit number
N:
15 14 13 12 11 10 9
Word N
0:
Always specify 0.
– : By other setting
Automatic Setting, Equality Layout
15
Start word for area 1 (BCD)
N+1
N+2
Area for area 1
Send size per node for area 1 (BCD)
N+3
N+4
Rightmost 4 digits of start word for area 2 (DM area) (BCD)
N+5
Area for area 2
N+6
Send size per node for area 2 (BCD)
N+7
First word to store link status (BCD)
15 14 13 12 11 10 9
N+8
16 15 14 13 12 11 10 9
N+9
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
N+10
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
N+11
--- --- 62 61 60 59 58 57 56 55 54 53 52 51 50 49
BCD: Set the value as binary-coded decimal.
Setting Range for
Automatic Setting,
Equality Layout
134
Set the following parameter in the DM Parameter Area of the PLC at the star-
tup node.
8
7
6
0 0
0
0
0
8
7
00
Leftmost digit of start word for
area 2 (BCD)
8
7
6
5
4
8
7
6
5
Item
Data link mode
Start word for area 1
Area for area 1
Send size per node for
area 1
Start word for area 2
5
4
3
2
1
0
0
0
0
Data link mode
001: Automatic setting, equality layout
101: Automatic setting, 1:N allocation
(000 is for manual setting. Settings other
than 000, 001, or 101 are invalid.)
0
3
2
1
0
4
3
2
1
Nodes to participate in the data links
The numbers indicate node numbers.
The status that is set determines whether the
node will participate in the data links.
Participate:
Not participate: OFF
Specify automatic (01).
Set the word address in BCD.
CIO Area: CIO 000 to CIO 6143
LR Area: LR 00 to 199 (*)
*: When a word between LR 000 and LR 199 is speci-
fied, the data link area will be allocated between
CIO 1000 and CIO 1199.
Set the area for area 1 in BCD.
CIO Area: 80
LR Area: 86
Area 1 not used: 00
Set the number of words in BCD between 0 and 1,000.
The total number of send words for area 1 and area 2
must not exceed 1,000.
When area 1 is not used, set to 0.
Set the word address in BCD.
DM Area: DM 0000 to DM 32767
EM Area: Banks 00 to 12, EM 0000 to EM 32767
Section 5-2
ON
Setting range