Setting Data Links
120
Setting item
First data link sta-
Set the first word to store data link status. An area of 16 words
tus word
is used.
IR Area:
LR Area:
DM Area: DM 0000 to DM 5984
EM Area: Banks 00 to 15, EM 0000 to EM 6128
*: When IR 000 is specified or when the default setting (
is left unchanged, the default first status word will be used.
Refer to 5-4 Checking Data Link Status for details.
Area 1 Data link
IR Area:
start word
LR Area:
DM Area: DM 0000 to DM 5999
EM Area: Banks 00 to 15, EM 0000 to EM 6143
The same area cannot be set for both area 1 and area 2. Set
different areas.
Number of
Remote nodes: 0 to the number of source words
words
Local node:
The total number of words in area 1 and area 2 in each node
must not exceed 1,000.
The numbers of words in both area 1 and area 2 in each node
must not be set to 0.
Offset
Remote nodes: 0 to one less than number of source words
Local node:
This setting is not required if an offset is not used.
Area 2 Data link
IR Area:
start word
LR Area:
DM Area: DM 0000 to DM 5999
EM Area: Banks 00 to 15, EM 0000 to EM 6143
The same area cannot be set for both area 1 and area 2. Set
different areas.
Number of
Remote nodes: 0 to the number of source words
words
Local node:
Set the number of words to be transmitted.
The total number of words in area 1 and area 2 in each node
must not exceed 1,000.
The numbers of words in both area 1 and area 2 in each node
must not be set to 0.
Offset
Remote nodes: 0 to one less than number of source words
Local node:
This setting is not required if an offset is not used.
Note a) The total number of words in data link send and receive areas
must not exceed 8,000 per node.
b) The following values must be satisfied for each node for the data
link area 1 and area 2 so that the final word in the data link does
not go beyond the last word in the PLC memory area.
Setting range
IR 001 to IR 220, IR 300 to IR 496 (*)
LR 00 to LR 48
(EM must be installed)
IR 000 to IR 235, IR 300 to IR 511
LR 00 to LR 63
(EM must be installed)
Set the number of words to be received.
0 to 1,000
Set the number of words to be transmitted.
Set the offset for the data to be received.
Cannot be set.
IR 000 to IR 235, IR 300 to IR 511
LR 00 to LR 63
(EM must be installed)
Set the number of words to be received.
0 to 1,000
Set the offset for the data to be received.
Cannot be set.
Section 5-2
––––
)