Cqm1H-Series Controller Link Unit - Omron SYSMAC CS1W-RPT01 Operation Manual

Controller link units
Hide thumbs Also See for SYSMAC CS1W-RPT01:
Table of Contents

Advertisement

Component Names and Functions
3-1-5

CQM1H-series Controller Link Unit

Wired Unit Indicators
Indicators
LED indicators that display the Unit and network status.
Node address switches
Two rotary switches. The node address of the Unit on the
Controller Link Network is set in 2-digit decimal.
Baud rate switch
bit/s
Terminating resistance switch
k
A slide switch. Use this switch to set the terminating resistance to ON for
the nodes at both ends of the Controller Link Network.
Terminal block for the communications cable
Terminals to connect to the Controller Link Network communications
cable (twisted-pair cable).
Name
RUN
(operating)
TER
(terminating
resistance)
ERC (communica-
tions error)
ERH
(PLC error)
INS
(network
participation)
M/A
(data link mode)
LNK
(data link)
SD
(send)
RD
(receive)
(Refer to pages 55, 274)
(Refer to page 103)
(Refer to page 103)
Color
Status
Green
Lit
Unit operating normally.
Not lit
Unit error.
Yellow
Lit
Terminating resistance switch ON.
Not lit
Terminating resistance switch OFF.
Red
Lit
Communications error, node address
setting error (same address set twice), or
hardware error.
Not lit
Normal operation
Red
Lit
PLC error, PLC interface error, or
EEPROM error
Not lit
No error.
Yellow
Lit
Unit is participating (inserted) in the net-
work.
Not lit
Unit is not participating (inserted) in the
network.
Yellow
Lit
Manual
(see note)
Not lit
Automatic
Yellow
Lit
Participating in data links.
Flashing
Error in data link tables.
Not lit
Not in a data link or data link inactive.
Yellow
Lit
Data transmission.
Not lit
No data transmission.
Yellow
Lit
Data reception.
Not lit
No data reception.
Section 3-1
(Refer to page 104)
(Refer to page 68)
Meaning
Note:
M/A is always not lit
when data links are not
active in the network.
55