Constructing Networks with Repeater Units
3-4-3

Terminating Resistance

T-Branch Wiring
Terminating
resistance: ON
Long-distance Wiring
Terminating
resistance: ON
84
The path from one node to another travels via three Repeater Units
(3 stages). This kind of network is NOT allowed.
Note If the Repeater Units are used incorrectly, communications errors may occur,
or nodes may not be able to participate in the network.
In a Wired Controller Link Network, turn ON the terminating resistance
switches only at the nodes at both ends of the network.
When Repeater Units are used to divide the network into multiple segments,
turn ON the terminating resistance switches of the nodes at both ends of each
segment. When a Repeater Unit is connected to the end of a segment, turn
ON the built-in terminating resistance switch of the Repeater Unit itself.
Connection examples are shown below.
Terminating
resistance: ON
Terminating
Segment 2
resistance: ON
Terminating resistance is turned ON at both ends of
each segment. (Repeater Units are also equipped
with a built-in terminating resistance switch.)
Terminating
resistance: ON
Segment 1
Terminating
resistance: ON
Segment 1
Terminating
resistance: ON
Terminating
resistance: ON
Segment 3
Terminating
resistance: ON
Segment 2
Terminating
CS1W-RPT01
resistance: ON
Repeater Unit
Section 3-4
Terminating
resistance: ON
CS1W-RPT01
Repeater Unit
Terminating
resistance: ON
Segment 3