Avaya Communication Server 1000M Single Group Manual page 65

Mini-carrier remote fundamentals
Hide thumbs Also See for Communication Server 1000M Single Group:
Table of Contents

Advertisement

3. Remove the front cover and all cards from the cabinet to make the cabinet lighter
4. Position the cabinet over the mounting bracket so that the bracket hook engages
5. Secure the cabinet to the wall by using two wood screws at the lower front of the
6. Install the 6 AWG copper ground wire between the approved building ground and
7. Install the power supply in the Pwr Sup slot and turn the power switch to OFF.
8. At the building ground end of the wire, use two fastening clamps to connect the wire
9. Disconnect the building ground wire at the ground lug on the cabinet and measure
10. For an AC system, connect the NTAK98AA Power Cord from the NTAK04 AC/DC
11. Measure the ground resistance between the ground lug at the bottom of the
12. Disconnect the power cord from the wall outlet for the AC system or the DC power
13. Reconnect the NTAK98AA supply power cord to the AC power outlet for an AC
This completes the cabinet installation and system ground test. You can now install the plug-
in cards.
Installing cards into the remote cabinet
The following steps show you how and where to install the NT5D67 RMI and other cards in
the remote cabinet. This document provides step-by-step card installation, which should be
followed when additional cards are installed or defective cards are replaced.
Mini-Carrier Remote Fundamentals
and to prevent card damage in case the cabinet drops during the installation
process.
the slot at the rear of the cabinet. The slot is located at the top center of the
cabinet.
cabinet.
the ground lug at the bottom of the cabinet.
to the building ground, insulate the connection with electric tape, and post a "DO
NOT DISCONNECT" tag.
the resistance between the tip of the disconnected ground wire and the ground lug
on the cabinet. If the resistance is more than 5 ohms, check the building ground
and the ground terminal at the AC wall outlet where the cabinet power cord is
connected.
power supply to the commercial AC power outlet.
For a DC system, connect the NTAK05 DC power converter cord to the DC power
source over the NTAK28AA Junction Box and the NTAK0410 power cable.
NTAK11BA cabinet and the ground prong on the cabinet power cord. It should
measure 0 ohms. If the resistance is greater than 0 ohms, check the ground terminal
on the power supply power connector for continuity to the cabinet.
source for the DC system and reconnect the 6 AWG ground wire to the cabinet
ground lug.
system or to the DC source for a DC system.
System installation
March 2013
65