RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
a
b
f
a Screw (upper air outlet assy)
b Upper air outlet assy
c Drain hose
d Damper motor wiring harness
e Screw (tie strap)
f Screw (lower air outlet assy)
g Lower air outlet assy
4 Put a small drain pan (or container) under the drain hose.
5 Remove the screw from the fixation bracket and pull the drain hose
downwards to remove it from the indoor unit.
6 Route the damper motor wiring harness out of the harness retainers and
remove the screw to disconnect the tie strap from the unit.
7 Remove the 2 screws and remove the lower air outlet assembly.
8 Remove the screw and remove the plate from the indoor unit heat exchanger.
c
a
b
a Screw (plate)
b Plate
c Indoor unit heat exchanger
d Piping fixture
e Flared joint
f Screw (ground wire)
9 Release the 2 hooks and remove the piping fixture.
10 Release the flared joint of the (refrigerant) liquid pipe and the gas pipe.
Disconnect the liquid and gas pipes from the refrigerant field piping. Plug the
refrigerant field pipes to prevent dirt from entering the pipes.
g
f
d
3
Components
|
a
d
e
c
f
e
e
Service manual
97