Daikin Perfera RXM R Series Service Manual page 127

Split r32
Table of Contents

Advertisement

To perform a diode module check
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
a
b
a + terminal
b – terminal
INFORMATION
When measuring on the front of the main PCB, make sure to locally remove the
protective varnish with the test leads of the multi meter.
Is the measured rectifier voltage
correct?
Yes
No
1 First check the rectifier voltage of the main PCB, see
4
procedures" [
 123].
INFORMATION
If the rectifier voltage is OK, the diode module is OK. If rectifier voltage is NOT OK,
replace the main PCB.
Below procedure describes how to check the diode module itself.
Prerequisite: Stop the unit operation via the user interface.
2 Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
3 Check the diode module in reference with the image and the table below.
3
|
Action
Perform a check of the power modules,
see
"Checking
procedures" [
Replace the main PCB, see
4
procedures" [
 131].
Components
4
 123].
"Repair
"Checking
Service manual
127