Daikin Perfera RXM R Series Service Manual page 168

Split r32
Table of Contents

Advertisement

3
|
Components
Service manual
168
Is the inductance measurement
correct?
No
Class 42~71 units
1 Check that the reactors are firmly installed on the main PCB.
a Reactor L803
b Reactor L804
2 Remove the main PCB, see
measuring points are ONLY reachable on the back side of the main PCB.
3 Measure the resistance of the reactor using a low ohm multi meter.
Result: The resistance MUST be as follows:
Measuring points
c‑d
e
c
a
a L803
b L804
c Measuring point
d Measuring point
e Measuring point
Is the resistance measurement correct? Action
Yes
Action
Replace the reactor, see
procedures" [
b
a
"Repair
procedures"  [
Resistance
15~25 mΩ
152~228 mΩ
e
d
c
d
e
b
Proceed with the next step.
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
"Repair
4
 169].
4
  138]. The reactor
d
e
d
c
e
c
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01