RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
8 Disconnect the DC fan motor connector S70 and measure the resistance on
the connector pins shown below. The measured resistance MUST be:
VDC
1
2
3
7
INFORMATION
The measured resistance values may deviate from the listed values due to instability
during the measurements.
DC fan motor resistance measurements
are correct?
Yes
No
9 Turn ON the power of the unit.
10 With the DC fan motor connector S70 disconnected from the main PCB,
measure the voltage on the connector pins 4-7 (= fan motor power supply) on
the main PCB.
Result: The voltage MUST be:
Unit
Class 42~60 + ARXM71R
RXM71R
11 Measure the voltage on the connector pins 4-3 (= fan motor control) on the
main PCB.
Result: The voltage MUST be 15±10% V DC.
Are both measured voltages correct?
Yes
No
12 Measure the voltage on the DC fan motor connector S70 pins 2-4 (= rotation
command) on the PCB.
Result: The measured voltage should be 0~7.5 V DC. It should NOT be 0 V DC.
Is the measured voltage 0 V DC?
Yes
No
13 Connect the DC fan motor connector to the PCB. Remove the plastic insert
from the connector for easier measurement.
Comm
4
4
4
4
Action
Continue with the next step.
Replace the DC fan motor, see
procedures" [
Voltage
200~390 V DC
342~408 V DC
Action
Continue with the next step.
Perform a check of the main PCB, see
"Checking
Action
Perform a check of the main PCB, see
"Checking
Continue with the next step.
3
Components
|
Resistance
>1 MΩ
>100 kΩ
>100 Ω
>100 kΩ
"Repair
4
 148].
4
procedures" [
 132].
procedures" [
4
 132].
Service manual
147