To perform a power module check
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
VDC
Com
b
a
d
c
c
a
4 If the diode module is NOT OK, replace the main PCB, see
4
procedures" [
 138].
Prerequisite: First check the rectifier voltage of the main PCB, see
4
procedures" [
 132].
Prerequisite: Stop the unit operation via the user interface.
1 Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
Power module IPM1 for compressor
1 Disconnect the compressor connector.
2 Check the power module IPM1 in reference with the image and the table
below.
a U
b V
c W
d DC+
e DC–
INFORMATION
When measuring on the front of the main PCB, make sure to locally remove the
protective varnish with the test leads of the multi meter.
VDC
Com
U
DC+
V
DC+
W
DC+
DC–
U
Ref
VDC
0.51~0.52 V
0.51~0.52 V
0.51~0.52 V
e
Ref
VDC
0.501 V
DC+
0.501 V
DC+
0.501 V
DC+
0.501 V
3
Components
|
Com
a
b
c
d
a
c
a
b
c
d
Com
U
V
W
U
DC–
Ref
O.L
O.L
O.L
"Repair
"Checking
Ref
O.L
O.L
O.L
O.L
Service manual
137