Daikin Perfera RXM R Series Service Manual page 167

Split r32
Table of Contents

Advertisement

RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
2 Remove the main PCB, see
measuring points are ONLY reachable on the back side of the main PCB.
3 Measure the resistance of the reactor using a low ohm multi meter.
Result: The resistance MUST be as follows:
Measuring points
c
d
a L803
b L804
c Measuring point
d Measuring point
Is the resistance measurement correct? Action
Yes
No
4 Measure the inductance of the reactor using an LCR meter.
Result: The inductance MUST be 80~100 µH.
a L803
b L803 measuring point
c L804
d L804 measuring point
Is the inductance measurement
correct?
Yes
"Repair
procedures"  [
Resistance
24~36 mΩ
68~102 mΩ
c
a
d
c
b
d
c
d
c
d
Proceed with the next step.
Replace the reactor, see
procedures" [
b
a
d
c
b
d
Action
Return to the troubleshooting of the
specific error and continue with the
next step.
3
Components
|
4
  131]. The reactor
"Repair
4
 169].
Service manual
167