Daikin Perfera RXM R Series Service Manual page 62

Split r32
Table of Contents

Advertisement

3
|
Components
Service manual
62
a
c
a Nut
b Compressor
c Damper
INFORMATION
The compressor dampers may look different.
3 Remove the caps from the compression pipe and suction pipe.
CAUTION
The oil in the compressor is hygroscopic. Therefore remove the caps from the
compressor pipes as late as possible.
4 Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
5 Wrap a wet rag around the compressor pipes and solder the compressor pipes
to the refrigerant pipes.
A
a
A Class 20~35 unit
a Compressor pipe
b
a
c
a
c
a
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01