Daikin Perfera RXM R Series Service Manual page 113

Split r32
Table of Contents

Advertisement

To check the wiring of the indoor unit power PCB
To check the fuse of the indoor unit main PCB
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
Is the correct spare part for the indoor
unit power PCB installed?
Yes
No
Prerequisite: First perform all earlier checks of the indoor unit main PCB, see
"Checking
procedures" [
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2 Check that no connectors or wires are damaged.
3 Check that the wiring corresponds with the wiring diagram, see
4
diagram" [
 223].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Yes
No
Prerequisite: First perform all earlier checks of the indoor unit main PCB, see
"Checking
procedures" [
1 Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
Action
Return to
procedures" [
power PCB and continue with the next
procedure.
Replace the indoor unit power PCB, see
"Repair
4
 110].
Action
No further actions required.
Return to
procedures" [
power PCB and continue with the next
procedure.
4
 110].
3
Components
|
"Checking
4
 110] of the indoor unit
4
procedures" [
 115].
"6.2  Wiring
"Checking
4
 102] of the indoor unit
Service manual
113