To perform an electrical check of the DC fan motor assembly
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
1 Visually check:
▪ For any burnt‑out part or wire. If found, replace the fan motor, see
4
procedures" [
 142].
▪ That fan motor fixation bolts are correctly installed and fixed. Correct as
needed.
2 Manually rotate the fan motor shaft. Check that it rotates smoothly.
3 Check the friction of the DC fan motor shaft bearing.
Is the DC fan motor shaft friction
normal?
Yes
No
1 First perform a mechanical check of the DC fan motor assembly, see
4
procedures" [
 140].
INFORMATION
Check the DC fan motor power supply (voltage) circuit on the PCB.
2 Turn ON the power of the unit.
3 Activate Cooling or Heating operation via the user interface.
4 Check the functioning of the outdoor unit fan.
Outdoor unit fan ...
Rotates continuously (without
interruption)
Does not rotate or rotates for a short
time
5 Turn OFF the unit via the user interface.
6 Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
7 Check that the DC fan motor connector is properly connected to the PCB.
8 Unplug the DC fan motor connector and measure the resistance between the
pins 1-3, 1-5, and 3-5 of the DC fan motor connector.
Result: All measurements MUST be 51.9~57.3 Ω.
3
|
Action
Perform an electrical check of the DC
fan motor assembly, see
4
procedures" [
 140].
Replace the DC fan motor assembly, see
4
"Repair
procedures" [
 142].
Action
DC fan motor assembly is OK. Return to
the troubleshooting of the specific error
and continue with the next procedure.
Continue with the next step.